Permit: T06EL00634

Parcel: 123130050


Addresses:

910 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00634

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2006 ELECTRIC - FINAL Approved
06/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTHING CORRECTED
05/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 14 WIRE ON 20A CB - PUT 15 AMP. BREAKER
2. COVER OPEN SLOT - WHERE BREAKER NOT INSTALLED.
3. AT J-BOX MUST GROUND BOX.
4. AT J-BOX BARE GROUND TIED TO NEUTRAL, TAPE NEUTRAL GREEN
5. 3/4" PVC'S OUT OF J-BOX TO BE SCHEDULE 80, AND SUPPORTED.
6. REMOVE UNUSED & UNTERMINATED WIRING OUTSIDE OF J-BOX.
NOTE TO OWNER - HAVE YOU ELECTRICIAN CORRECT AND RECALL.
04/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE HOME
04/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE HOME
04/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
GATES ARE LOCKED, DOGS IN YARD, NO ANSWER @ DOOR PLEASE RESCHEDULE.