Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL00634
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) ROOF JACK SET DOWN WHEN ROOF REPAIRED 2) CALL FOR FINAL ONCE CHANGE OVER COMPLETE |
|
04/06/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED ROOF JACK 2. RISER PER TEP SPEC'S REQUIRED TO BE 2" 3. IF PVC TO BE USED OUTSIDE ABOVE GROUND ITS REQUIRED TO BE SCH 80. 4. SUPPORT PVC W/IN 3' OFF ENDS 5. GI BOX TO BE SUPPORTED, NOT OFF FITTING ALONE. 6. USE A ROMEX CONNECTOR WHERE GROUNDS ENTER BOTTOM OF SERVICE. 7. FOR TRANSFER OF POWER IF BREAKER BOX TO BE USED - BREAKERS MUST BE USED OR PROPER J-BOX. 9. TWO SUPPORTS REQUIRED WHERE ROOF ON RISER. |