Permit: T06EL00634

Parcel: 123130050


Addresses:

910 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL00634

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) ROOF JACK SET DOWN WHEN ROOF REPAIRED
2) CALL FOR FINAL ONCE CHANGE OVER COMPLETE
04/06/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ROOF JACK
2. RISER PER TEP SPEC'S REQUIRED TO BE 2"
3. IF PVC TO BE USED OUTSIDE ABOVE GROUND ITS REQUIRED TO BE SCH 80.
4. SUPPORT PVC W/IN 3' OFF ENDS
5. GI BOX TO BE SUPPORTED, NOT OFF FITTING ALONE.
6. USE A ROMEX CONNECTOR WHERE GROUNDS ENTER BOTTOM OF SERVICE.
7. FOR TRANSFER OF POWER IF BREAKER BOX TO BE USED - BREAKERS MUST BE USED OR PROPER J-BOX.
9. TWO SUPPORTS REQUIRED WHERE ROOF ON RISER.