Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY SERVICE DISCONNECT AS "SERVICE DISCONNECT" NOT "MAIN" - NEC 230.70(B) 2. YOU HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTORS - READ NEC 250.6 |
|
| 06/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. IDENTIFY PANEL DIRECTORY. 2. SECURE TO STRUCTURE OR BURY BONDING AND G.E.C 3. REMOVE BOND WIRE IN SERVICE RACEWAY IT CREATES A PARALLEL PATH FOR CURRENT NEC 250.6 4. IDENTIFY SERVICE DISCONNECT AS SUCH. |
|
| 05/31/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |