Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND BOTH ENDS OF GROUNDING ELECT. CONDUCTORS SLEEVE (1/2" E.M.T) PER CHOKE EFFECT (SEE N.E.C 250.64 E) 2. CONDUCTORS (CURRENT CARRYING) WHERE COMBINED NEED TO BE SIZED TO ALLOW FOR ADJUSTMENT FACTOR PER TABLE 310.15 (B) (2) (A) 2002 NEC RESCHEDULE FINAL INSP. WHEN CORRECTIONS MADE 740-6970 |