Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/12/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND BOTH ENDS OF GROUNDING ELECT. CONDUCTORS SLEEVE (1/2" E.M.T) PER CHOKE EFFECT (SEE N.E.C 250.64 E)
2. CONDUCTORS (CURRENT CARRYING) WHERE COMBINED NEED TO BE SIZED TO ALLOW FOR ADJUSTMENT FACTOR PER TABLE 310.15 (B) (2) (A) 2002 NEC
RESCHEDULE FINAL INSP. WHEN CORRECTIONS MADE 740-6970