Permit: T06EL00622

Parcel: 113093600


Addresses:

1213 E COPPER ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00622

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IN GUTTER, GROUND LOOSE ON GROUND SCREW, TO MANY GROUNDS UNDER WIRE NUT, NEUTRAL WITH GROUND, PROVIDE GFI PROTECTION FOR EXTERIOR OUTLET UNDER GUTTER AND N.P. COVER
2. BRANCH CKT'S IN RACEWAY NEED TO BE DERATED NEC 310.15
3. MAX 15 AMP FOR 14 GA INTERIOR WIRING.
4. MAKE SURE PANEL DIRECTORY IS CORRECTLY IDENTIFIED.
5. SECURE BOND WIRE TO GAS.
6. TIGHTEN GAS AND WATER BOND SET SCREW.