Permit: T06EL00620

Parcel: 138110170


Addresses:

6136 S NOGALES HY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO COMPLIANCE WITH NOTES LAST INSP. TO AVOID PAYING REINSPECTION FEES, BE SURE YOU ARE READY BEFORE CALLING FOR INSPECTION.
04/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PERMANENT ADDRESS LABEL ON SERVICE DISCONNECT.
2. GROUNDING ELECTRODE CONDUCTOR CUT - REGROUND SYSTEM.
3. IMPROPER WIRING METHOD WHERE FEEDER EXITS CONDUIT AND ENTERS BLD. SHOULD HAVE APPROVED FITTINGS.
4. AREA IN FRONT OF SERVICE NEEDS TO BE CLEARED OUT.
5. SEAL UNUSED OPENINGS IN J-BOX INSIDE.
6. OUTSIDE SECURITY LIGHTS IN FRONT IS IN VIOLATION OF COT LIGHTING ORDINANCE, REPAIR & POINT DOWN OR INSTALL SHIELD.
7. INSTALL W/P BOX & COVER FOR COOLER.
04/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
A REINSPECTION FEE WILL BE ASSESSED NEXT INSP. IF NO ACCESS.
RECALL BUILDING MUST BE OPEN
NO MESSAGES.
04/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
UNIT MUST BE OPEN FOR INSPECTION
RECALL INSPECTION