Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO COMPLIANCE WITH NOTES LAST INSP. TO AVOID PAYING REINSPECTION FEES, BE SURE YOU ARE READY BEFORE CALLING FOR INSPECTION. |
|
| 04/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PERMANENT ADDRESS LABEL ON SERVICE DISCONNECT. 2. GROUNDING ELECTRODE CONDUCTOR CUT - REGROUND SYSTEM. 3. IMPROPER WIRING METHOD WHERE FEEDER EXITS CONDUIT AND ENTERS BLD. SHOULD HAVE APPROVED FITTINGS. 4. AREA IN FRONT OF SERVICE NEEDS TO BE CLEARED OUT. 5. SEAL UNUSED OPENINGS IN J-BOX INSIDE. 6. OUTSIDE SECURITY LIGHTS IN FRONT IS IN VIOLATION OF COT LIGHTING ORDINANCE, REPAIR & POINT DOWN OR INSTALL SHIELD. 7. INSTALL W/P BOX & COVER FOR COOLER. |
|
| 04/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* A REINSPECTION FEE WILL BE ASSESSED NEXT INSP. IF NO ACCESS. RECALL BUILDING MUST BE OPEN NO MESSAGES. |
|
| 04/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT MUST BE OPEN FOR INSPECTION RECALL INSPECTION |