Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06EL00619
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
07/05/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. SERVICE RISER MUST BE BONDED NEC 250.92 2. DRIVE GROUND RODS STRAIGHT - NEC 250.53 3. BOND GAS PIPE TO SERVICE - NEC 250.104 4. INSTALL WARNING RIBBON IN TRENCH - NEC 300.5 OK TO COVER TRENCH UP TO GROUND RODS. *NOTE: ALL WIRING MUST BE DONE BY LICENSED ELEC. CONTRACTOR. |
|
04/21/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THERE MUST BE A PERMIT ACTIVE FOR REMODEL OF HOUSE WHICH INCLUDES ALL TRADES PRIOR TO ALLOWING A CHANGE OVER OF SERVICE. OFFICE VERIFICATION SHOWS NO ACTIVE COMBO PERMIT. 2. GROUND RODS ARE REQUIRED TO BE DRIVEN STRAIGHT INTO GROUND UNLESS ROCK PROHIBITS THERE IS NO INDICATION OF ROCK IN TRENCH. |