Permit: T06EL00615

Parcel: 113111820


Addresses:

1710 E WAVERLY ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00615

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
NICE JOB
04/27/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EDDIE - NEC 250.32 WHEN A BUILDING IS SUPPLIED FROM A SEPARATE STRUCTURE AND A GREEN GROUND WIRE IS RUN TO 2ND BUILDING THEN EPR 250.32 B-1 THE GROUND FROM ELECTRODES (THE RODS) IS NOT CONNECTED TO THE NEUTRAL AT 2ND BLD., THIS CAUSES A PARALLEL PATH BACK TO MAIN SERVICE IN CASE OF A FAULT OR SHORT.
2. NEED TO REMOVE #4 FROM RODS AND GAS BOND AND JUST LAND THEM ON LOWER GROUND BAR ONLY & LEAVE NEUTRAL ISOLATED, ALSO REMOVE JUMPER FROM RIGHT SIDE NEUTRAL BAR TO CAN IN THIS CASE NEUTRAL AT HOUSE REMAINS ISOLATED, IF A GREEN GROUND HAD NOT BEEN BROUGHT FORM SERVICE THEN ALL ITEMS ABOVE ARE TIED TOGETHER ELIMINATING PARALLEL PATH BACK TO SERVICE.