Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00615
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NICE JOB |
|
04/27/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EDDIE - NEC 250.32 WHEN A BUILDING IS SUPPLIED FROM A SEPARATE STRUCTURE AND A GREEN GROUND WIRE IS RUN TO 2ND BUILDING THEN EPR 250.32 B-1 THE GROUND FROM ELECTRODES (THE RODS) IS NOT CONNECTED TO THE NEUTRAL AT 2ND BLD., THIS CAUSES A PARALLEL PATH BACK TO MAIN SERVICE IN CASE OF A FAULT OR SHORT. 2. NEED TO REMOVE #4 FROM RODS AND GAS BOND AND JUST LAND THEM ON LOWER GROUND BAR ONLY & LEAVE NEUTRAL ISOLATED, ALSO REMOVE JUMPER FROM RIGHT SIDE NEUTRAL BAR TO CAN IN THIS CASE NEUTRAL AT HOUSE REMAINS ISOLATED, IF A GREEN GROUND HAD NOT BEEN BROUGHT FORM SERVICE THEN ALL ITEMS ABOVE ARE TIED TOGETHER ELIMINATING PARALLEL PATH BACK TO SERVICE. |