Permit: T06EL00606

Parcel: 121090440


Addresses:

5320 E LINDEN PL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/13/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/09/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR TO RESCHEDULE
06/02/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONTRACTOR DID NOT RETURN CALL TO SCHEDULE INSPECTION AS PER MESSAGE REQUEST.
05/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SECURE CABLES TO BOX 312.5
2. BOND JUNCTION BOX 250.148
3. COMPLETE PREVIOUS ITEM MARKED.
05/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
* FINISH GROUNDING ELECTRODE SYSTEM.
* BOND GAS PIPING.
* BOND WATER.
* DE RATE CONDUCTORS SHARING CONDUIT PER TABLES 310-15 (B)(2)(A) ADJUSTMENT 10-20 CONDUCTORS 50%
21-30 CONDUCTORS 45%