Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00601
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DENIED - THIS IS AN UNGROUNDED SYSTEM THE NEUTRAL BAR SHALL NOT HAVE A STRAP TIED TO ENCLOSURE. 2. TOP SIDE 20 AMP BKR - TAPE CONDUCTOR WHERE DAMAGED & SHOWING COPPER. |
|
04/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED - NO ACCESS - BUILDING ADDRESS NEEDS TO BE CLEARLY POSTED. LEFT MESSAGE ON 977-2497 |