Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DENIED - THIS IS AN UNGROUNDED SYSTEM THE NEUTRAL BAR SHALL NOT HAVE A STRAP TIED TO ENCLOSURE. 2. TOP SIDE 20 AMP BKR - TAPE CONDUCTOR WHERE DAMAGED & SHOWING COPPER. |
|