Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/18/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE 8/3 CABLE USED OUTSIDE DOES NOT SHOW A LISTING FOR OUTDOOR USE. 2. THE PHYSICAL PROTECTED USED TO PROTECT CABLE AS IT COMES DOWN THE SIDE OF THE SERVICE IS NOT LISTED FOR ELECTRICAL INSTALLATION INTO SERVICE. 3. GROUND ELECTRODE CONDUCTOR COMING FROM GROUND RODS INTO SERVICE ENCLOSURE SHALL BE LANDED ON NEUTRAL BAR - (PURPOSE TO CONNECT TO SERVICE NEUTRAL) ONLY CONNECT TO ENCLOSURE. TYPE TC-ER |
|
| 04/18/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) PROVIDE AN APPROVED METHOD OF PHYSICAL PROTECTION FOR CABLES UP TO 8' AFF COMING DOWN AND BELOW SERVICE EXISTING METHOD OF PROTECTION INSUFFICIENT 2) TALKED TO CONTRACTOR-FLYNN ELECTRIC WILL CONSTRUCT A SOFFIT TYPE TROUGH WITH REMOVEABLE COVERS TO PROTECT FEEDERS |
|
| 04/14/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* PROVIDE RACEWAY UP TO ROOF OVERHANG TO PROTECT CABLES FROM PHYSICAL DAMAGE. |