Permit: T06EL00597

Parcel: 127121680


Addresses:

5720 E HOLMES ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE FINISH PREVIOUS ITEM #4-9
IF ONLY 2 CIRCUITS ADDED PLEASE ADD TO PERMIT.
2. PROTECT CONDUCTOR AND CABLES AT TOP PLATE 300.4
3. WHY IS A NEUTRAL IN A GROUND LUG AT THE JUNCTION BOX.
4. CLEAN SURFACE UNDER LUGS IN JUNCTION BOXES 250.12
5. PLEASE VERIFY CONDUCTOR FILL FOR CONDUIT AND JUNCTION BOXES.
03/31/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY NEW GROUNDING ELECTRODE SYSTEM.
2. GROUND RODS TO BE AS CLOSE AS POSIBLE TO SERVICE.
3. CANNOT ENTER THROUGH TOP OF PANEL WITH LOAD CONDUCTORS AS PER MANUFACTURERS INSTRUCTIONS.
4. VERIFY GAS BOND.
5. SECURE CABLES TO JUNCTION BOX.
6. IDENTIFY CIRCUIT CONDUCTORS TO VERIFY PHASING FOR NEUTRAL LOADS.
7. WHY ARE NEUTRALS CONNECTED TO GROUNDS?
8. TIGHTEN LOOSE FITTINGS.
9. PLEASE VERIFY PERMIT FOR NEW WIRING TO INTERIOR.