Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE FINISH PREVIOUS ITEM #4-9 IF ONLY 2 CIRCUITS ADDED PLEASE ADD TO PERMIT. 2. PROTECT CONDUCTOR AND CABLES AT TOP PLATE 300.4 3. WHY IS A NEUTRAL IN A GROUND LUG AT THE JUNCTION BOX. 4. CLEAN SURFACE UNDER LUGS IN JUNCTION BOXES 250.12 5. PLEASE VERIFY CONDUCTOR FILL FOR CONDUIT AND JUNCTION BOXES. |
|
| 03/31/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY NEW GROUNDING ELECTRODE SYSTEM. 2. GROUND RODS TO BE AS CLOSE AS POSIBLE TO SERVICE. 3. CANNOT ENTER THROUGH TOP OF PANEL WITH LOAD CONDUCTORS AS PER MANUFACTURERS INSTRUCTIONS. 4. VERIFY GAS BOND. 5. SECURE CABLES TO JUNCTION BOX. 6. IDENTIFY CIRCUIT CONDUCTORS TO VERIFY PHASING FOR NEUTRAL LOADS. 7. WHY ARE NEUTRALS CONNECTED TO GROUNDS? 8. TIGHTEN LOOSE FITTINGS. 9. PLEASE VERIFY PERMIT FOR NEW WIRING TO INTERIOR. |