Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL NON GROUNDING CIRCUITS NEED TO HAVE NON-GROUNDING RECEPTACLES OR GFCI TYPE RECEPTACLES OR GROUND PER N.E.C - I.R.C 2. INSTALL BOX EXTENSIONS OR FLASH RINGS - SLEEVES WHERE BOXES ARE MORE THAN 1/4" FROM FACE OR FINISHED WALL. 3. J-BOXES ARE OVERFILLED 4. NEW PLASTIC BOXES THROUGHOUT (HOUSE BUILT IN 1957)? 5. EQUIP. GROUNDING CONDUCTOR SPLICES W/OUT WIRE NUTS OR CRIMP SLEEVES. 6. ROMEX CONNCTORS NEEDED WHERE N.M ENTERS BOXES, STEP LIGHTS, FAN BOXES, HOOD. 7. GROUND ALL SWITCHES WHERE AN EQUIP. GROUNDING CONDUCTOR IS AVAILABLE. 8. OPEN DRYWALL ON NEW C.FANS, RECESSED LIGHTS, LAUNDRY CIRCUITS, ALL HOMERUNS ALL NEW WIRING SO WE CAN DO A THOROUGH - COMPLETE INSPECTION ON ELECTRICAL SYSTEM. 9. NEW WIRING IN BEDROOMS NEED TO BE ARC FAULT PROTECTED 10. KITCHEN TO BE WIRED USING #12 WIRE (20 AMPS) PER N.E.C - I.R.C 11. KITCHEN COUNTER RECEPTACLES TO BE GFCI PROTECTED. 12. SORRY TO HAVE TO GO THROUGH THIS TO THIS EXTENT, BUT THIS IS THE ONLY WAY WE CAN DO A COMPLETE INSPECTION AND ASSURE TO THE FUTURE OWNER - OCCUPANTS THAT THIS INSTALLATION IS SAFE AND KEEP ALL LIABILITY TO A MIN. TO THE CITY OF TUCSON. |