Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE, WELL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | ELECTRIC - SERVICE, WELL | Approved | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - SERVICE, WELL | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUIT ABOVE GRADE TO PREVENT BREAKAGE. 2. SUPPLIMENTARY GROUND ROD (2ND) TO BE MINIMUM 6' APART ALSO, FLUSH TO GRADE. 3. #10 WIRE AMPACITY IS 30 AMPS. 4. A PERMANENT ADDRESS LABEL IS NEEDED. |