Permit: T06EL00557

Parcel: 135051220


Addresses:

6325 E CALLE PEGASO

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/02/2006 ELECTRIC - SERVICE UPGRADE Approved
05/19/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
N.E.C REQUIRES AN EQUIPMENT GROUNDING CONDUCTOR TO BE INSTALLED IN ADDITION TO THE METAL CONDUIT FOR THE POOL EQUIPMENT (MIN. #12 AND INSULATED AND COLOR TO BE GREEN)
05/12/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SCREW OR RIVET THE METAL ADDRESS LABEL TO THE METER SECTION.
2. TAP CON CONNECTION AT BOTTOM RIGHT CORNER OF PANEL IS NOT ACCEPTABLE.
3. CONDUCTOR SHEATH NEEDS TO ENTER INTO PANEL FOR SUBPANEL FEED.
4. POOL CIRCUIT NEEDS EQUIP. GROUNDING CONDUCTOR.
5. YOUR MISSING YOUR 2ND GROUND ROD.
6. USE MURRAY BREAKERS.
7. INSTALL CONNECTOR OR BUSHING WHERE CONDUCTORS ENTER THROUGH REAR OF PANEL.
8. INSTALL GAS BONDING (#4 CONDUCTOR).
04/26/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEP'S POWER LINE FEED NEEDS TO BE A MIN. OF 23' FROM THE WATER'S EDGE.
2. SERVICE NEEDS TO BE ATTACHED DIRECTLY TO MASONRY
3. ALL BOXES AND FITTINGS ETC. MUST BE APPROVED FOR WET LOCATIONS.
4. TEP & CODE REQUIRE A METAL ADDRESS BE DIRECTLY ATTACHED AT SERVICE.
5. INSTALL #4 GROUNDING ELECTRODE CONDUCTOR TO 2 GROUND RODS 8' X 5/8" SPACED A MIN. OF 6' APART AND THE INTERIOR WATER & GAS PIPING NEED TO BE BONDED TO THE ELECT. SERVICE (USE #4 COPPER CONDUCTOR).
6. BREAKER FILLER BLANKS FELL OUT (THEY MAY NOT BE MURRAY BOARD.
7. USE MURRAY BREAKERS.
8. METER BASE IS NOT TO EXCEED 6'3" TO CENTER PER T.E.P