Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/27/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/14/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT CONDUITS WITHIN 3' OF BOXES.
2. TIGHTEN LOOSE FITTINGS.
3. SEAL TIGHT SHEATHING TO SEAT INTO FITTING.
4. PLEASE LABEL ALL EQUIPMENT.
5. REJECTION PINS NEEDED AT SERVICE.
6. NEED ELECTRICIAN PRESENT TO OPEN EQUIPMENT.
05/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK U.G METER BASE TO X-FORMER
- OK GROUNDING AT SERVICE.
- GFI RECEPTS. REQUIRED FOR TEMP. POWER