Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00554

Parcel: 122171820


Addresses:

3355 E CAMDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/11/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. EQUIPMENT GROUND FOR SUB-PANEL HAS OBJECTIONABLE CURRENT ON IT. NEC 250.6
2. I NEED TO SEE SPLICE FROM OLD FEEDER TO NEW FEEDER. IT APPEARS NEUTRAL AND EQUIPMENT GROUND ARE NOT SEPARATED ALL THE WAY THROUGH SUB-PANEL.
NEUTRAL = 1.4 AMPS
EQUIPMENT GROUND = .7 AMPS
03/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLASTIC ANCHOR HOLDING HANGER FOR 2" RISER INSUFFICIENT HAS ALREADY PULLED OUT OF WALL.
2. INSTALL ROOF JACK & SEAL ON TOP OF ROOF.
3. WHITE WIRE ON 40 AMP 2 POLE FOR SUB-PANEL MUST BE TAPED BLACK OR RED.
4. EQUIPMENT GROUND BEING USED AS NEUTRAL ON 40 AMP SUB-PANEL?