Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. EQUIPMENT GROUND FOR SUB-PANEL HAS OBJECTIONABLE CURRENT ON IT. NEC 250.6 2. I NEED TO SEE SPLICE FROM OLD FEEDER TO NEW FEEDER. IT APPEARS NEUTRAL AND EQUIPMENT GROUND ARE NOT SEPARATED ALL THE WAY THROUGH SUB-PANEL. NEUTRAL = 1.4 AMPS EQUIPMENT GROUND = .7 AMPS |
|
| 03/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLASTIC ANCHOR HOLDING HANGER FOR 2" RISER INSUFFICIENT HAS ALREADY PULLED OUT OF WALL. 2. INSTALL ROOF JACK & SEAL ON TOP OF ROOF. 3. WHITE WIRE ON 40 AMP 2 POLE FOR SUB-PANEL MUST BE TAPED BLACK OR RED. 4. EQUIPMENT GROUND BEING USED AS NEUTRAL ON 40 AMP SUB-PANEL? |