Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 06/02/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* CONTRACTOR (DALE) WITH RAYS WILL CALL WHEN READY. |
|
| 05/31/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 05/26/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MAST BOND LUG SCREW IS STRIPPED/BROKE NEC 250.4 (A)(5) 2. SEAL PLUBS ON TOP OF SERVICE GUTTER NEC 110 3. IDENTIFY SERVICE DISCONNECT NEC 230.70 (B) 4. FINISH INTERIOR WIRING 5. SERVICE INSPECTION ONLY AT THIS TIME. |
|
| 04/20/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/19/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/05/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |