Permit: T06EL00543

Parcel: 122181110

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/29/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL LIGHTING OUTLET NEEDED IN PANEL ROOM.
2. INSTALL HARD WIRED SMOKE DETECTORS IN BEDROOM AND OUTSIDE BEDROOM.
OK TO DRYWALL/PATCH AFTER CORRECTIONS.
3. INSTALL PROPER CONNECTOR FOR PANEL RACEWAY.
4. GROUND ALL METAL BOXES.
06/02/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/24/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
AT SERVICE:
1. SERVICE GUTTER AND MAST NEED TO BE BONDED NEC 250.92
2. SERVICE CONDUCTORS AND BRANCH CKT CONDUCTORS NOT ALLOWED IN SAME RACEWAY/GUTTER NEC 230.7
3. NEED BUSHING FOR #4 AND LARGER WIRE NEC 300.4(F)
4. IDENTIFY SERVICE DISCONNECT AND THE LOAD IT SERVES NEC 230.70 B
5. BOND NEUTRAL TO ENCLOSURE NEC 250.24(B)
6. NEED EQUIPMENT GROUND FOR FEEDER NEC 250.32 (B)(U)
7. TRENCH FOR FEEDER TO GUEST HOUSE NEEDS TO MEET REQUIREMENTS OF NEC 300.5(A)
AT GUEST HOUSE:
1. HAVE OVERFILLED BOXES NEC 314.16
2. NEED MINIMUM 6" OF CONDUCTORS IN BOXES NEC 300.14
3. USE PROPER TOOL FOR CRIMP SLEEVES AND TIGHTEN WIRE NUTS NEC 110.0
4. ALL METAL BOXES NEED TO BE GROUNDED PROPERLY NEC 314.4
5. INSTALL NAIL PLATE AND PROTECT OPEN ROMEX NEC 334
NEED QUALIFIED ELECTRICIAN
INSPECTION NOT COMPLETE - WILL CONTINUE