Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* TEP STILL HAS NOT RESPONDED |
|
| 06/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WAITING ON TEP |
|
| 05/10/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) TEP LINES PER 680.10 |
|
| 05/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MEET WITH CONTRACTOR TO DISCUSS JOB. |
|
| 04/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CLEAN SURFACE UNDER LUG. 2. FINISH PREVIOUS ITEMS #1, 6 AND 7 |
|
| 03/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN CLEARANCE TO EDGE OF WATER 680.10 ALL CONDUCTORS. 2. MAINTAIN WORKING CLEARANCE 110.26 3. USE APPROVED FITTING 4. A SEALING DEVICE ABOVE CURRENT CARRING PARTS IS NEEDED. 5. BOND JUNCTION BOX ENCLOSURE. 6. MAINTAIN CLEARANCES ON ARAL CONDUCTORS 7. CONDUCTORS AND SPLICES TO BE LISTED FOR OUTDOOR USE. 8. SUPPORT CONDUIT ON SIDE OF PANEL. |