Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00532

Parcel: 126090390


Addresses:

4101 E KINGS RD

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
TEP STILL HAS NOT RESPONDED
06/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WAITING ON TEP
05/10/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) TEP LINES PER 680.10
05/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MEET WITH CONTRACTOR TO DISCUSS JOB.
04/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CLEAN SURFACE UNDER LUG.
2. FINISH PREVIOUS ITEMS #1, 6 AND 7
03/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN CLEARANCE TO EDGE OF WATER 680.10 ALL CONDUCTORS.
2. MAINTAIN WORKING CLEARANCE 110.26
3. USE APPROVED FITTING
4. A SEALING DEVICE ABOVE CURRENT CARRING PARTS IS NEEDED.
5. BOND JUNCTION BOX ENCLOSURE.
6. MAINTAIN CLEARANCES ON ARAL CONDUCTORS
7. CONDUCTORS AND SPLICES TO BE LISTED FOR OUTDOOR USE.
8. SUPPORT CONDUIT ON SIDE OF PANEL.