Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PER MANUFACTURERS INSTRUCTION YOU CANNOT ENTER THROUGH METER SECTION OF ALL IN ONE. 2. PLEASE VERIFY CONDUCTORS ARE NOT LARGER THAN #6 FOR SPLICES IN BLUE WIRE NUT. 3. BOND JUNCTION BOXES 4. WE HAVE UNSAFE CONDITIONS WITH NM CABLE AT JUNCTION BOX IN CORNER. 5. MAINTAIN CLEARANCE TO GROUND FOR SERVICE CONDUCTORS PER 230.24 |