Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PER MANUFACTURERS INSTRUCTION YOU CANNOT ENTER THROUGH METER SECTION OF ALL IN ONE.
2. PLEASE VERIFY CONDUCTORS ARE NOT LARGER THAN #6 FOR SPLICES IN BLUE WIRE NUT.
3. BOND JUNCTION BOXES
4. WE HAVE UNSAFE CONDITIONS WITH NM CABLE AT JUNCTION BOX IN CORNER.
5. MAINTAIN CLEARANCE TO GROUND FOR SERVICE CONDUCTORS PER 230.24