Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE DISCONNECT IS MOUNTED TO HIGH (OVER 7') 2. BOTH UNITS WATER AND GAS SYSTEMS NEED TO BE BONDED TO SERVICE (SEPARATE SYSTEMS). 3. TIGHT BOND CLAMPS SCREWS 4. NEED SUNLIGHT RESISTANT SERVICE WIRE 5. REMOVE FIELD INSTALLED BONDING JUMPER - ALREADY HAS FACTORY JUMPER INSTALLED IN UTILITY SECTION. |