Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/29/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE DISCONNECT OVER 7' 2. BOND BOTH UNITS GAS AND WATER TO SERVICE 3. TIGHTEN BOND CLAMPS 4. USE SUNLIGHT RESISTANT SERVICE WIRE. 5. REMOVE FIELD INSTALLED BONDING JUMPER - ALREADY HAS FACTORY INSTALLED M.B.J. |