Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL00530
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
03/29/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE DISCONNECT OVER 7' 2. BOND BOTH UNITS GAS AND WATER TO SERVICE 3. TIGHTEN BOND CLAMPS 4. USE SUNLIGHT RESISTANT SERVICE WIRE. 5. REMOVE FIELD INSTALLED BONDING JUMPER - ALREADY HAS FACTORY INSTALLED M.B.J. |