Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/25/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS PIPING AS PER NOTE #3 LAST INSP. 2. #4 NOTE NO COMPLIANCE 3. INSTALL CABLE OR ROMEX CONNECTORS AT NEW SUB-PANEL & REMOVE TIE BETWEEN NEUTRAL & GROUND BUSS. |
|
| 09/21/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS MUST HAVE PROPER CLAMPS FOR EACH CONNECTION TO GROUND ROD. 2. IMPROPER FITTING AT BACK OF PANEL, USE APPROVED CLAMP, OUTER SHEATH OF CABLE MUST ENTER PANEL. HOW DID YOU RUN WIRE TO OTHER UNIT? MUST INSPECT WIRING METHOD. 3. BOND WATER & GAS PIPING 4. TIE GROUNDS TOGETHER FOR SERVICE GROUNDING SYSTEMS PER 250 N.E.C 5. INSTALL PERMANENT ADDRESS LABELS. |