Permit: T06EL00529

Parcel: 132110290


Addresses:

2202 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/27/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/25/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS PIPING AS PER NOTE #3 LAST INSP.
2. #4 NOTE NO COMPLIANCE
3. INSTALL CABLE OR ROMEX CONNECTORS AT NEW SUB-PANEL & REMOVE TIE BETWEEN NEUTRAL & GROUND BUSS.
09/21/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS MUST HAVE PROPER CLAMPS FOR EACH CONNECTION TO GROUND ROD.
2. IMPROPER FITTING AT BACK OF PANEL, USE APPROVED CLAMP, OUTER SHEATH OF CABLE MUST ENTER PANEL. HOW DID YOU RUN WIRE TO OTHER UNIT? MUST INSPECT WIRING METHOD.
3. BOND WATER & GAS PIPING
4. TIE GROUNDS TOGETHER FOR SERVICE GROUNDING SYSTEMS PER 250 N.E.C
5. INSTALL PERMANENT ADDRESS LABELS.