Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL00526
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
03/14/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TEP TIE IN 2) SEPERATE GROUNDS AND NEUTRALS IN SUB-PANEL |
|
03/08/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
03/06/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/22/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 2 GROUND RODS REQUIRED 6' MIN. APART 2. BOND WATER & GAS PIPING 3. SUPPORT RISER BELOW ROOF LIN - USE 1/4" BOLTS 4. NEUTRAL CONDUCTOR MUST BE WHITE NOT GREEN #4 MINIMUM. 5. STRAP #4 GROUND TO WALL 6. NEED TO SEE NEW WIRING OR FEEDER TERM. INTO SUB-PANEL. |