Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUB-PANEL FEEDER NEEDS TO BE ON 60 AMP BREAKER ISOLATE GROUNDS & NEUTRAL IN SUB-PANEL |
|
| 03/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRE FED THRU WRONG END OF ACORN CLAMP ONLY ONE WIRE ALLOWED PER CLAMP. 2. NO COMPLIANCE WITH LAST INSP. NOTES 3. WIRING TO SUB PANEL CANNOT BE EXPOSED OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO DO THE WORK. |