Permit: T06EL00510

Parcel: 113010490

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/26/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND GAS AND WATER FOR EACH UNIT TO EACH UNIT SUB-PANEL IN TIGHTEN CONNECTIONS.
2. USE ONLY BREAKERS LISTED FOR USE ON SUB-PANEL (NOT SQ.D HOMLINE) ETC.
3. IDENTIFY ALL BRANCH CKTS IN PANELS.
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PREVIOUS CORRECTIONS NOT MADE
1. PROVIDE PREVIOUS INSPECTION REPORT.
2. NEED ELECTRICIAN ON SITE.
05/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE TO CONTRACTOR - DID YOU KNOW THESE PANELS ARE RATED NEMA 1 FOR INDOOR USE ONLY
OWNER TO OBTAIN PERMIT FOR RE-WIRE FOR INTERIOR & EXTERIOR OF UNITS.
05/09/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
VERIFY NOTES #2 & #3 INSP. ON 4/4/06
05/01/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*