Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND GAS AND WATER FOR EACH UNIT TO EACH UNIT SUB-PANEL IN TIGHTEN CONNECTIONS. 2. USE ONLY BREAKERS LISTED FOR USE ON SUB-PANEL (NOT SQ.D HOMLINE) ETC. 3. IDENTIFY ALL BRANCH CKTS IN PANELS. |
|
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PREVIOUS CORRECTIONS NOT MADE 1. PROVIDE PREVIOUS INSPECTION REPORT. 2. NEED ELECTRICIAN ON SITE. |
|
| 05/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE TO CONTRACTOR - DID YOU KNOW THESE PANELS ARE RATED NEMA 1 FOR INDOOR USE ONLY OWNER TO OBTAIN PERMIT FOR RE-WIRE FOR INTERIOR & EXTERIOR OF UNITS. |
|
| 05/09/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* VERIFY NOTES #2 & #3 INSP. ON 4/4/06 |
|
| 05/01/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |