Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH CORRECTIONS #3,4,6,7,8 FROM PREVIOUS INSP. ALSO, GAS BOND CLAMP SCREWS ARE LOOSE PAY REINSPECTION FEE. |
|
| 03/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE 1/4" HARDWARE TO SECURE RISER 2. 1/2 CONDUIT NEW FEED TO NEW AC UNIT TO BE SUPPORTED OFF ROOF. 3.#4 BARE COPPER TO WATER LINE CANNOT BE STRUNG OVER ROOF AND LEFT 4. PERMIT FOR NEW UNIT REQUIRED 5. NO GAS LINE BOND 6. LABEL LOWER 50A 2 POLE BREAKER AS TO WHAT IT FEEDS 7. CANNOT FIND LISTING ON SERVICE ENTRANCE CONDUCTORS BEING SUNLIGHT RESISTANT. 8. FIX DOOR ON PANEL SO IT OPENS FREELY. |
|
| 03/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL WHEN READY |