Date Description Inspector Results Comments
12/29/2009 ELECTRIC - SERVICE UPGRADE Approved
04/03/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE 2ND GROUND ROD - MUST BE 6' APART & TIED TOGETHER.
2. INSTALL WATER BOND.
3. MUST OBTAIN PERMIT FOR AC AND HEATING UNITS, REWIRE OF HOUSE (PANEL SHOWS ALL NEW WIRING).
4. NEW DUCT WORK
5. NEW PLUMBING.