Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T06EL00457
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
03/13/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MOUNT HALL SMOKE DETECTOR 2. INSTALL PROPER FUSE SIZE IN SUB-PANEL 3. INSTALL WEATHERPROOF BOX AND COVER FOR WASHER RECEPTACLE, (OUTDOOR NEEDS GFI PROTECTION) 4. CLEAR BRUSH IN FRONT OF SERVICE EQUIPMENT 5. OUTLET UNDER EXTERIOR PANEL HAS OPEN SPLICE AND BOX NEEDS TO BE WEATHERPROOF AND GFI PROTECTION. 6. CLEAN/REPLACE PAINTED OVER OUTLETS. |
|