Permit: T06EL00439

Parcel: 10713242M


Addresses:

325 E FONTANA PL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/17/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
03/16/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
NEED TO HAVE A LICENSED ELECTRICAL CONTRACTOR DO ALL ELECTRICAL WORK
03/15/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
1. PROVIDE WORKING SPACE IN FRONT OF SERVICE NEC 110.26
2. BOND GAS ON CUSTOMER SIDE AND REMOVE PAINT
NEC 250.12, NEC 250.104(B)
3. DRIVE RODS FLUSH NEC 250.53 (6)
4. INSTALL METAL ADDRESS TAG ON SERVICE