Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL00437
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
03/23/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3/22/06 -- NOT READY PER CONTRACTOR WILL HOLD PERMIT AND INSPECT 3/23/06 IN A.M. 3/23/06 1. NEED DEAD FRONT COVER ON SERVICE DISCONNECT ENCLOSURE FOR TWO STORY BUILDING OK TO OCCUPY THIS BUILDING AFTER COVER IS INSTALLED. |
|
03/22/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/21/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROGRESS IS GOOD ALTHOUGH NOT COMPLETE 1. CHECK ALL UNITS FOR ANY CODE VIOLATIONS, SMOKE DETECTORS WORKING, CORRECT OUTLET POLARITY ETC... 2. INSTALL DEAD FRONT COVERS AND IDENTIFY ALL BRANCH CKTS'S AND DISCONNECTS. 3. CHECK FOR OBJECTIONABLE CURRENT ON BONDING JUMPER 4. CHECK RACEWAYS/BOXES FOR KO PLUGS AND COVERS AND RACEWAYS COMPLETE. |
|
03/16/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TALKED WITH WARD, PROGRESS IS GOOD. WARD WILL CALL FOR INSPECTION WHEN READY |