Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE PROPER TYPE BREAKER FOR PANEL (GE-NOT HOMELINE 2. EXTEND RACEWAY FOR SUB-PANEL INTO NEW J-BOX 3. GROUND NEW J-BOX WITH FEEDER EQUIPMENT GROUND 4. PROVIDE WIRE NUT OR EQUAL FOR ROMEX EQUIPMENT GROUNDS IN J-BOX. 5. SCRAPE PAINT FROM UNDER BOND CLAMPS 6. SECURE BOX FOR GFI UNDER PANEL |