Permit: T06EL00428

Parcel: 120051360


Addresses:

4500 S 19TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/25/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/03/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- ALL BREAKERS MUST BE SAME BRAND AS PANEL -
SEE NOTE #1 FIRST INSPECTION.
- ALL NEUTRAL WIRES TO BE WHITE - USE TAPE
A RE-INSPECTION FEE WILL BE ASSESSED IF NEXT INSPECTION NON-COMPLIANT.
04/25/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND RODS CANNOT BE CLOSER THAN 6' AS PER NOTE LAST INSP.
2. BOND GAS PIPING.
3. BOND BUSHING REQUIRED AS PER NOTE #4
4. GROUND WIRES TO GROUND RODS CANNOT BE SPLICED UNDER PANEL MUST BE CONTINUOUS TO CONNECTION IN PANEL.
04/18/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. ALL CIRCUIT BREAKERS MUST BE SAME BRAND AS PANEL.
2. INSTALL GROUNDING SYSTEM, BOND WATER & GAS, 2 GROUND RODS 6' MIN. APART.
3. SERVICE RE-ENERGIZED PRIOR TO INSPECTOR APPROVAL.
4. BOND BUSHING REQUIRED WHERE USING REDUCING WASHERS.