Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2/0 COPPER CONDUCTORS IN METER ENCLOSURE HAVE STRANDS CUT OFF AT TERMINATIONS, FULL STRANDS TO BE INSTALLED INTO TERMINATION 2) GE 30 AMP BREAKER NOT TO BE INSTALLED IN MURRAY PANEL 3) USE A ROMEX CONNECTOR WHERE GROUNDS ENTER AT BOTTOM OF SERVICE 4) SUPPORT 3/4" LB OR 3/4" EMT BY LB 5) FINISH STRAPPING GROUND WIRE TO STRUCTURE BELOW SERVICE |