Permit: T06EL00418

Parcel: 106120700

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00418

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
03/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSTALL PROPER SIZE FUSES FOR BRANCH CIRCUITS IN SUB-PANEL
2) INSTALL SMOKE DETECTOR IN BEDROOM AND HALLWAY
3) REPAIR ALL INTERIOR AND EXTERIOR LIGHT FIXTURES AS NEEDED
4) REPAIR/MAKE SAFE ALL INTERIOR AND EXTERIOR OPEN WIRING