Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL00413
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) TIGHTEN 2" CHASE NIPPLES SO THE ENAMEL PAINT IS CUT AT PANEL AND GUTTER 2) INSTALL RAISED METAL ADDRESS TAG PER IRC & TEP |
|
07/12/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. DOOR TO FREELY OPEN 90 DEG. 2. USE AN APPROVED FITTING FOR CONNECTION OF GUTTER TO PANEL. 3. FILL UNUSED OPENINGS IN GUTTER. 4. PLEASE VERIFY CIRCUIT LOADS FOR BREAKERS WITH 2 CONDUCTORS. 5. FINISH GROUNDING 6. USE ONLY LISTED OPENINGS AND CONNECTIONS FOR METER AREA. |