Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 08/09/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BOND GAS AND WATER PIPES TO SERVICE AND CALL FOR FINAL WHEN CHANGE OVER IS COMPLETE. DON'T FORGET TO SEAL TEMP FEED OPENING IN SIDE OF SERVICE |
|
| 04/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THIS GE ENCLOSURE IS NOT LISTED FOR SIDE ENTRIES ONLY UNDERGROUND NOT EVEN TEMPORARY SERVICE. 2. GAS BOND MISSING. 3. SERVICE ENTRANCE WIRE #1 TOO SMALL MUST BE 2/0 COPPER. 4. WHERE CHASE NIPPLES ARE USED CLOSED NIPPLES WITH LOCK NUTS ARE TO BE USED. |