Permit: T06EL00393

Parcel: 121090580


Addresses:

5308 E LESTER PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/01/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY GAS & WATER BONDING
2. LABEL BREAKERS
3. RACEWAY TO BE NON FLEXIBLE FOR CABLES 373.5(C) EXCEPTION
4. MAINTAIN WORKING CLEARANCES PER 110.26
5. A SEALING DEVICE WILL BE NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS.