Permit: T06EL00392

Parcel: 123023200


Addresses:

2501 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/01/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. NEED GAS BOND
2. MAINTAIN WORKING SPACE IN FRONT OF SERVICE
3. RISER HARDWARE TO BE 1/4" MINIMUM
4. DERATE CONDUCTORS IN CONDUIT ACROSS ROOF FOR AMBIENT TEMPERATURE AND CURRENT CURRING CONDUCTORS 310.15 & 16
5. SEALING DEVICE TO BE EFFECTIVE
6. A PERMIT IS NEEDED FOR WORK BEING DONE TO INTERIOR PLEASE VERIFY
7. N.M. CABLE AMPACITY TO BE AS PER 330.80