Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/01/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. NEED GAS BOND 2. MAINTAIN WORKING SPACE IN FRONT OF SERVICE 3. RISER HARDWARE TO BE 1/4" MINIMUM 4. DERATE CONDUCTORS IN CONDUIT ACROSS ROOF FOR AMBIENT TEMPERATURE AND CURRENT CURRING CONDUCTORS 310.15 & 16 5. SEALING DEVICE TO BE EFFECTIVE 6. A PERMIT IS NEEDED FOR WORK BEING DONE TO INTERIOR PLEASE VERIFY 7. N.M. CABLE AMPACITY TO BE AS PER 330.80 |