Permit: T06EL00370

Parcel: 12007255B

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/03/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/17/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SPLIT BOLT SPLICE UNDERGROUND NOT APPROVED FOR WATER BOND CONNECTION TO GROUND SYSTEM.
03/07/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
WIRE FOR WATER & GAS BONDING IMPROPERLY TERMINATED TO GROUND ROD AND AT WATER & GAS PIPING.
03/03/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. BOND WATER & GAS PIPING
2. INSTALL SEALING LOCKNUTS OR HUBS AT CONDUIT TERMINATIONS ABOVE SERVICE ENCLOSURE.
3. INSTALL PERMANENT ADDRESS LABELS ON SERVICE WITH UNIT #. MUST BE SCREWED OR RIVETED.
4. GROUNDING ELECTRODE CONDUCTOR MUST BE TERMINATED AT NEUTRAL LUG PROVIDE BY MANUF. AT NEUTRAL BUSS.