Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/17/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SPLIT BOLT SPLICE UNDERGROUND NOT APPROVED FOR WATER BOND CONNECTION TO GROUND SYSTEM. |
|
| 03/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* WIRE FOR WATER & GAS BONDING IMPROPERLY TERMINATED TO GROUND ROD AND AT WATER & GAS PIPING. |
|
| 03/03/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. BOND WATER & GAS PIPING 2. INSTALL SEALING LOCKNUTS OR HUBS AT CONDUIT TERMINATIONS ABOVE SERVICE ENCLOSURE. 3. INSTALL PERMANENT ADDRESS LABELS ON SERVICE WITH UNIT #. MUST BE SCREWED OR RIVETED. 4. GROUNDING ELECTRODE CONDUCTOR MUST BE TERMINATED AT NEUTRAL LUG PROVIDE BY MANUF. AT NEUTRAL BUSS. |