Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A BOND BUSHING IS NEEDED AT SERVICE NIPPLE 250.92 2. SCREW IN BOND SCREW 3. SECURE GROUNDING CONDUCTORS TO PANEL. 4. SUPPORT CONDUIT AND TIGHTEN LOOSE FITTINGS ON SIDE OF PANEL. 5. FILL UNUSED OPENING IN BOX. 6. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 7. A PERMANENT METAL ADDRESS LABEL IS NEEDED. 8. CORRECTLY LABEL ALL BREAKERS. |