Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/10/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHEET METAL SCREW NOT ALLOWED FOR GROUNDING 2. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL AS PER 250.122 3. SEPARATE GROUNDING CONDUCTORS AND IDENTIFY UNGROUNDED CONDUCTORS TO VERIFY PHASING 4. LABEL BREAKERS 5. RISER HARDWARE TO BE 1/4" MINIMUM |