Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 03/13/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 02/28/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1. SERVICE CONDUCTOR CLEARANCES TO GROUND TO BE AS PER 230.24 2. RISER HARDWARE TO BE 1/4" MINIMUM 3. RECEPTACLE COVER AS PER 406.8 4. LABEL BREAKERS 5. CHASE NIPPLE NOT AN APPROVED FITTING WITH 2.3 6. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 7. CABEL SHEATHING TO BE 1/4" INTO CABINET 8. FILL UNUSED OPENING WITH NEW COMBUSTIBLE PRODUCT IN BACK OF PANEL. 9. WE HAVE COT INSULATION FOR UNGROUNDED CONDUCTOR 10. SUPPORT GAS BOND CONDUCTOR OFF OF ROOF 11. CLEAN SURFACE UNDER GAS BOND CLAMP 12. PLEASE VERIFY PERMITS FOR WORK ON INTERIOR WITH NEW NM CABLES 13. WHAT IS EXPOSED NM AT SIDE OF SERVICES. |