Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE LOCATION IN VIOLATION OF WORKING CLEARANCE YOU MUST HAVE 36" IN FRONT AND 30" WIDE OF CLEAR SPACE - TREE IN SPACE. 2. BUBBLE COVER REQUIRED FOR GFI RECEPT. BELOW PANEL BOX NOT SUPPORTED. 3. EXPOSE GROUND RODS FOR INSP. MUST HAVE 2 RODS 8' LONG, 6' MIN. SPACED APART. 4. ID THE CIRCUIT BREAKERS & THE NEUTRAL WIRE FOR RISER CONDUCTORS MUST BE I.D'D WITH WHITE TAPE. BOTH ENDS. 5. USE MIN. 1/4" BOLTS TO SUPPORT RISER CONDUIT. |