Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MAKE MAST RAINTIGHT (NO SET SCREW CONNECTOR). 2. BOND GAS AND WATER WITH #4 COPPER. 3. 20 AMP. MAX OVERCURRENT ON #12 CU WIRE. |
|
| 05/10/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |