Permit: T06EL00331


Addresses:

3001 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00331

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTORS IN RACEWAYS TO BE DERATED PER
NEC 310.15 B 2 A
2. NEED BUSHINGS #4 & LARGER CONDUCTOR NEC 300.4
3. PROPERLY INSTALL IN-USE COVERS NEC 110.3
4. CORRECTLY IDENTIFY PANEL DIRECTORY NEC 408.4
5. MC TO BE INSTALLED/STRAP/SECURE NEC 330.30
6. CHECK BOX FILL IN TWO MAIN J-BOXES & CHECK EQUIPMENT GROUND CONNECTIONS.
08/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/10/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ALL INSTALLATION ACCESSIBLE FOR INSPECTION
PROVIDE LADDER AND HAVE CEILING OPEN WHERE REQUIRED
MAKE SURE ALL IS PER PLAN AND WORKING PROPERLY
CHECK TO SEE IF FIRE CAULKING IS REQUIRED