Inspection History Details
Permit: T06EL00331
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTORS IN RACEWAYS TO BE DERATED PER NEC 310.15 B 2 A 2. NEED BUSHINGS #4 & LARGER CONDUCTOR NEC 300.4 3. PROPERLY INSTALL IN-USE COVERS NEC 110.3 4. CORRECTLY IDENTIFY PANEL DIRECTORY NEC 408.4 5. MC TO BE INSTALLED/STRAP/SECURE NEC 330.30 6. CHECK BOX FILL IN TWO MAIN J-BOXES & CHECK EQUIPMENT GROUND CONNECTIONS. |
|
| 08/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE ALL INSTALLATION ACCESSIBLE FOR INSPECTION PROVIDE LADDER AND HAVE CEILING OPEN WHERE REQUIRED MAKE SURE ALL IS PER PLAN AND WORKING PROPERLY CHECK TO SEE IF FIRE CAULKING IS REQUIRED |