Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL00323
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/29/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR INTERIOR OF UNIT #3 1. MAKE UP WIRING 2. ROMEX TO BE STAPLED WITHIN 12" OF BOXES -- NEC 334.30 3. INSTALL NAIL PLATES AS REQUIRED -- 300.4 4. BRANCH CKT'S IN ATTIC RACEWAYS TO BE DERATED - NEC 310.15 5. ROMEX TO BE PROTECTED BY ATTIC ACCESS -- NEC 334.23 6. INSTALL UNIT #'S ON UNITS. 7. REMOVE DRYWALL FOR WALL INSPECTION 8. NEED INTERCONNECTED SMOKE DETECTORS EACH BEDROOM AND HALLWAY WITH BOXES. 9. KITCHEN WIRING TO COMPLY 210. PART III |