Permit: T06EL00323

Parcel: 117021250


Addresses:

1014 N 7TH AV #03


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL00323

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR INTERIOR OF UNIT #3
1. MAKE UP WIRING
2. ROMEX TO BE STAPLED WITHIN 12" OF BOXES -- NEC 334.30
3. INSTALL NAIL PLATES AS REQUIRED -- 300.4
4. BRANCH CKT'S IN ATTIC RACEWAYS TO BE DERATED -
NEC 310.15
5. ROMEX TO BE PROTECTED BY ATTIC ACCESS -- NEC 334.23
6. INSTALL UNIT #'S ON UNITS.
7. REMOVE DRYWALL FOR WALL INSPECTION
8. NEED INTERCONNECTED SMOKE DETECTORS EACH BEDROOM AND HALLWAY WITH BOXES.
9. KITCHEN WIRING TO COMPLY 210. PART III