Permit: T06EL00321

Parcel: 117021250


Addresses:

1014 N 7TH AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00321

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2008 ELECTRIC - FINAL Approved
01/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/03/2008 ELECTRIC - FINAL Partial Approval ALL ITEMS FROM INSPECTION 10/07/07 CORRECTED, ELECTRICAL FINAL OK SUBJECT TO GENERAL CONTRACTOR OR OWNER. SHEET ROCKING OFF ISLAND COUNTER IN KIT & BATHROOM WALL AND CLOTHES WASHER & DRYER ROOM
10/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CHECK OUTDOOR GFI RECEPTACLES SECURED TO BUILDING SURFACE
2. INSTALL MISSING DEVICE PLATES
3. INSTALL FIXTURE TRIMS
4. CHECK WATTAGE ON CLOSET LAMPS
5. OPEN GROUND ON GFI RECEPT KITCHEN
6. OUTDOOR WALL SCONCE INSTALLED UPSIDE DOWN
7. INSTALL DISPOSAL
8. FINISH SHEET ROCKING
9. FINISH KITCHEN ISLAND & INSTALL ISLAND RECEPTACLES
10. SMOKE DETECTORS TO BE INTERCONNECTED
11. LABEL ALL CIRCUITS AT PANEL
12. INSTALL FILLER PLATES ON OPEN BREAKER POSITION AT PANEL
13. SMOKE DETECTOR CIRCUIT TO BE AFCI
14. WIRING IN ATTIC NOT PER CODE
15. INSTALL K.O SEALS IN JUNCTION BOXES
16. NEED TO DERATE CONDUCTORS IN 1 1/2" EMT TO JUNCTION BOXES IN ATTIC
17. INSTALL SERVICE RECEPTACLE FOR AC UNIT
18. PROVIDE PAPERWORK/PREVIOUS INSPECTONS SHOWING OUTDOOR LIGHTING RACEWAYS INSPECTED
19. GENERAL LIGHTING & GATE OPERATURE SHOULD BE ON HOUSE PANEL NOT TENANTS PANEL
20. GROUND ALL METAL BOXES
02/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE CONDUCTOR TAPS NOT TO BE MADE IN SERVICE PANEL #3 GROUND BAR
GROUNDING ELECTRODE CONDUCTOR TAPS MAY BE MADE BY A SPLIT BOLT TO EACH SERVICE TO A UNSPLICED GROUNDING ELECTRODE CONDUCTOR SEE ILLSTR 250 NEC
2. VERIFY WATER PIPE BONDING.
3. GFI RECEPT. COVER TO BE BUBBLE TYPE - PER 2002 NEC
4. SPLICES BEHIND PANELS NOT ALLOWED. ROMEX SHEATH TO EXTEND 1/4" INTO ENCLOSURE.
5. CHANGE DESCRIPTION TO 200 AMP UPGRADE NOT 100 AMP