Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06EL00307
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 05/11/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1. GROUND RODS TO BE MINIUMU 6' APART & SECURE GROUNDING ELECTRODE CONDUCTOR. 2. TIGHTEN RISER FITTING. 3. USE APPROVED FITTING WITH LB. CHASE NIPPLE NOT APPROVED. 4. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 5. PROTECT CONDUCTORS AT FITTING #8 AND LARGER. 6. ONLY ONE CONDUCTOR PER ACORN CLAMP. 7. PLEASE UNCOVER SECONDARY CONDUITS FOR INSPECTION 8. GROUND JUNCTION BOX ENCLOSURES. |